NAC445A.6691. Water wells: Construction near certain other sources of water.  


Latest version.
  • If a water well is drilled within 1/4 mile of a perennial stream, river, lake, unlined reservoir or unlined canal:

         1. There must be no perforations in the production casing from ground level to a depth of 100 feet.

         2. The well must have a sanitary seal to a depth of 100 feet.

         3. A permanent conductor casing may be used to convey the gravel pack to the 100-foot level.

     (Added to NAC by Bd. of Health, eff. 2-20-97)