Nevada Administrative Code (Last Updated: January 6, 2015) |
Chapter445A Water Controls |
PUBLIC WATER SYSTEMS |
Design, Construction, Operation and Maintenance |
NAC445A.67035. Pumping facilities: Gauges and meters.
-
1. Each pump must:
(a) Have a standard pressure gauge on its discharge line located upstream from any check valve.
(b) Except for a vertical turbine pump, have a:
(1) Standard pressure gauge on its suction line if the pump is in suction head; or
(2) A compound pressure gauge on its suction line if the pump is in suction lift.
2. Each pumping station must have a device for measuring the rate of flow of discharge and the total flow.
3. A meter or flow sensor must have straight pipes installed both upstream and downstream. The length of the pipes must:
(a) Comply with the specifications of the manufacturer of the meter or flow sensor; or
(b) In the absence of those specifications, be at least five times the diameter of the pipes.
(Added to NAC by Bd. of Health, eff. 2-20-97)