Nevada Administrative Code (Last Updated: January 6, 2015) |
Chapter445A Water Controls |
PUBLIC WATER SYSTEMS |
Design, Construction, Operation and Maintenance |
NAC445A.6717. Separation of lines: Sewer main crossing water service lateral.
-
1. If a sewer main crosses a water service lateral, the sewer main must be located:
(a) At least 18 inches lower than the water service lateral, as measured vertically from the exterior walls of the pipes; or
(b) If compliance with paragraph (a) is impracticable, in such a manner as is authorized by the Division.
2. If a water service lateral is in place at the time a sewer main is constructed and must be relocated to comply with this section, the relocation must be performed:
(a) With the approval of and in accordance with the procedures and standards of the supplier of water; or
(b) If compliance with paragraph (a) is impracticable, in such a manner as is authorized by the Division.
(Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm’n by R194-08, 10-27-2009)