NAC449.7332. Mechanical systems.  


Latest version.
  •      1. Before the completion and acceptance of a facility, all mechanical systems must be tested, balanced and operated to demonstrate to the owner or his or her representative that the installation and performance of the systems conform to the requirements of the plans and specifications.

         2. The owner must be furnished with a complete set of operating maintenance and preventative maintenance instructions and parts listed with numbers and descriptions for each piece of equipment.

         3. Facilities must be built and maintained in accordance with NFPA 101: Life Safety Code adopted by reference pursuant to NAC 449.0105.

         4. All air supply and air exhaust systems must be mechanically operated.

         5. Hot water must be:

         (a) Maintained at a temperature of:

              (1) Not more than 125°F (52°C) for clinical use;

              (2) Not more than 180°F (82°C) for dishwashing;

              (3) Not more than 110°F (43°C) for toilet, bath and shower areas and any lavatories equipped for washing hands which are used by patients; and

              (4) At least 150°F (66°C) for use in the laundry.

         (b) Provided with at least 25 pounds of pressure.

     (Added to NAC by Bd. of Health by R066-04, eff. 8-4-2004)