NAC461A.190. Sewer connections.  


Latest version.
  •      1. Each mobile home stand must be provided with a sewer connection that is located and aligned to permit attachment in a workmanlike manner to a mobile home occupying the mobile home stand.

         2. Each mobile home stand must be provided with a sewer riser that has a diameter of at least 4 inches. This riser must be located within 4 feet of the mobile home stand and the drain outlet of the pipe must be in a position that is approximately vertical.

         3. The line connecting to the sewer riser must have a minimum diameter of at least 3 inches. The slope of any part of the line from the mobile home to the connection must be at least one-fourth of an inch per foot. The sewer connection must consist of one pipe without branch fittings. All the joints in a sewer pipe must be sealed to prevent leaks and any invasion of insects.

         4. The sewer riser must be capped when a mobile home does not occupy the mobile home stand. The rim of the riser must be protected from damage above the ground.

     (Added to NAC by Mfd. Housing Div., eff. 6-29-84; A by R055-02, 7-18-2002)