NAC477.568. Sprinkler system for certain child care facilities used after midnight.


Latest version.
  • Child care facilities which are used for child care between the hours of 12 a.m. and 6 a.m. and care for seven or more children must have a sprinkler system installed which conforms to N.F.P.A. Standard 13, 13D or 13R, 2010 editions, as applicable, and the requirements of the International Building Code, 2006 edition. The sprinkler system must be tied into the fire alarm system so that activation of any portion of the sprinkler system will activate the alarm system.

     (Added to NAC by St. Fire Marshal, eff. 3-9-89; A by R220-99, 9-25-2000; R062-04, 9-3-2004; R090-10, 12-30-2011)