NAC590.456. Installation of cabinet for LP gas cylinder exchange.  


Latest version.
  •      1. Except as otherwise provided in subsection 2, each cabinet installed for LP gas cylinder exchange must have a clearance of not less than 5 feet on the front and each side of the cabinet.

         2. Clearance between the sides of each cabinet for LP gas cylinder exchange is not required if the cabinets are installed in a group.

         3. A sign must be posted on the front of each cabinet for LP gas cylinder exchange. The sign must:

         (a) Be white with red letters that are not less than 2 inches in height.

         (b) Contain the words “NO SMOKING,” “FLAMMABLE” and “PROPANE.”

         (c) Include a telephone number for emergencies.

         4. Any open flame must be kept at least 10 feet from each cabinet for LP gas cylinder exchange.

     (Added to NAC by Bd. for Reg. of Liquefied Petrol. Gas by R073-10, eff. 12-16-2010)