NAC618.5120. Requirements for barricades.
Latest version.
- A barricade for a building or magazine containing explosives materials must effectively screen the building from the other buildings, public ways and magazines in the explosives manufacturing plant. A barricade that is made of mounds of revetted walls of earth must be not less than 3 feet in thickness. A barricade for a building or magazine containing explosives materials will be considered to be in compliance with this section if a straight line from the top of any side wall of the building or magazine to the eave line of any other building, or to a point that is 12 feet above the center line of a public way, passes through the barricade for the building or magazine.
(Added to NAC by Div. of Industrial Relations by R109-00, eff. 9-6-2001)