Nevada Administrative Code (Last Updated: January 6, 2015) |
Chapter459 Hazardous Materials |
STORAGE TANKS |
NAC459.9948. Underground storage tanks: Under-dispenser container required for certain motor fuel dispensers.
-
1. Except as otherwise provided in NAC 459.9949, an under-dispenser container is required for all motor fuel dispensers that are installed on or after July 1, 2008, at a location where there was no previous dispenser or at a location to replace an existing dispenser and the equipment used to connect the dispenser to the underground storage tank is replaced.
2. An under-dispenser container must:
(a) Be liquid-tight on its sides, bottom and at any penetrations;
(b) Be compatible with the substance conveyed by dispenser piping;
(c) Allow for monitoring or visual inspection and access to the components in the containment system; and
(d) At all times, be made available for inspection by the Division.
(Added to NAC by Environmental Comm’n by R005-08, eff. 4-17-2008)